Psychrometric Chart Webinar Beyond The Basics

Описание к видео Psychrometric Chart Webinar Beyond The Basics

See all my HVAC Webinars at: 👉https://insightpartners.lpages.co/👈
In this webinar we move beyond Basic Psychrometrics and discuss the following:

Part 1 Air Mixing. Mixing air on the psychrometric chart.
Part 2 Calculating SHR. The sensible heat ratio is one of the most important HVAC aspects of the psych chart.
Part 3 Calculating CFM and sizing the airflow of the hvac system. Using the sensible heat equation to calculate air quantity in cubic feet per minute (CFM). See equation below.
Part 4 Calculating tons of refrigeration using the enthalpy of air as shown on the psychrometric chart and the total cooling equation. See equation below.

Takeaway equations from this webinar:
Sensible cooling (Btu/hr) = 1.085 x CFM x dT
Total cooling (Btu/hr) = CFM x 4.5 x dH
1 Ton of Refrigeration = 12,000 Btu/hr
1 BTU = Amount of heat required to raise (or lower) the temperature of one pound of water 1F
Enthalpy = sensible heat + latent heat

Visit my YouTube Channel for all of my training videos.
http://bit.ly/2W3z8no

Connect with me on Linkedin:
  / tony-mormino  

Subscribe to this YouTube Channel:
http://bit.ly/2SYI2zm

Tony Mormino
[email protected]