EXCESSIVE COMPRESSOR CONDENSATION, AND COLD TO TOUCH - DETERMINING CAUSE

Описание к видео EXCESSIVE COMPRESSOR CONDENSATION, AND COLD TO TOUCH - DETERMINING CAUSE

Mike was sent to this location for a PM. When he noticed ice cold temperatures and excessive condensation on compressor #1, he determined there was likely an issue with either airflow, refrigerant charge, or a metering device. Initial assumption was excessive refrigerant due to the apparent recent compressor replacement. Visual inspection revealed adequate airflow, but the issue turned out to be a TXV bulb that had come out of position. .