Frost Fighter Heaters - Smoke Test and How to Adjust the Air Settings (IDF Oil/Diesel)

Описание к видео Frost Fighter Heaters - Smoke Test and How to Adjust the Air Settings (IDF Oil/Diesel)

The intention of this Service Video is to demonstrate the procedure to perform a smoke test and to adjust the air settings using both the air shutter and the air band.
Use for FrostFighter IDF and OHV Oil/Diesel Fired units.

Procedure:
00:21 Step 1: Start the unit using the toggle switch found on the side of the burner.

00:49 Step 2: Insert smoke test strip into air pump slot.

01:14 Step 3: Insert the air pump nozzle into the flue stack through a hole along the surface, and pump it exactly ten times.

01:54 Step 4: Remove the test strip and compare the discoloration on the paper with the reference scale.
NOTE: If your resulting paper discoloration is above 1 on the smoke scale, then air adjustments must be made.

02:40 Step 5: Using a wrench, loosen the locking fastener on the side (shutter) or ring (band).

02:57 Step 6: With the fastener now loose, we can begin rotating the tab (for the shutter) or the entire ring (for the band) to the desired setting. A scale on the side of the burner housing is used as a gauge.

03:11 Step 7: Once you have set the air shutter or air band to the desired level, tighten the fastener you loosened earlier.