Fire Suppression Test #5

Описание к видео Fire Suppression Test #5

Hey everyone. Hope you are well. Today Wilson & I test 2 Halon 1301 Systems protecting 2 large magnetic laboratories. The way these systems is in the following steps:

Upon the first alarm, a bell / strobe will activate to notify of a fire. This bell goes on infinitely.

Upon the second alarm, the system goes into pre-discharge. The horn strobe next to the bell will begin to sound. This signifies that there is 20 seconds until discharge.


After 20 Seconds, the discharge light one the panel activates, the solenoids are energized (if connected to the bottle, it would dump the Halon), and the Horn Strobes outside the protected area begin to sound to signify that discharge has begun.


Any alarms on this system will result in the activation of the building fire alarm.


Equipment:

Fenwal 2210 Special Hazard Control Panel

Fenwal PSD-7130 Photoelectric Smoke Detector

Fenwal CPD-7129 Ionization Smoke Detector

Fenwal CPD-7054 Ionization Smoke Detector

Fenwal CPD-7051 Ionization Smoke Detector

Fenwal/FCI MS-2H Halon Manual Release Pull Station

Wheelock MBS-G6-24-WS Bell Strobe

Wheelock 7002T-24 (Halon Lettering)

Wheelock NS-24-MCW

Fenwal Abort Switch (Model Unknow)

Fenwal Halon 1301 (500 lbs tank)

Fenwal Halon 1301 (300 lbs tank)

Fenwal 890181 Electric Solenoid Control Head