Differential Pressure Flow Transmitter Re-Range Calculation | Revised Flow Range Of DPT

Описание к видео Differential Pressure Flow Transmitter Re-Range Calculation | Revised Flow Range Of DPT

This instrumentation video provides detail explanation about differential pressure flow transmitter Re-Range Calculation. Know more about the basics of Differential pressure transmitter .For more videos related to range calculation of DPT , do subscribe our channel

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Video Content:
Example: A flow measurement system comprising of an orifice plate has an input of 0 to 100 Inches WC representing a flow of 1 to 200 L/S. What differential pressure is required to increase the flow range to 0 to 300 L/S?
Square Root of Revised DP= (Revised Flow)/(Existing Flow) *Square Root Of Existing DP
Square Root of Revised DP = 300/200 *√100
Square Root of Revised DP = 1.5 * 10
√(Revised DP) = 15
Revised DP = 〖15〗^2
Revised DP(URV) = 225 Inches WC

Square Root of Revised DP= (Revised Flow)/(Existing Flow) *Square Root Of Existing DP
Square Root of Revised DP = 0/1 *√0
Revised DP(LRV) = 0 Inches WC
For Flow Range: 0 L/S TO 300 L/S= Differential Pressure Range: LRV = 0 Inches WC
URV =225 Inches WC
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
If you have missed our most recent videos, then watch them here:
1. Thermocouple Two Wire Temperature Transmitter Calibration - Omega TX93 Calibration
   • Thermocouple Two Wire Temperature Tra...  
2. What is a PID Controller | Proportional Band | Integral Action | Derivative Action
   • What is a PID Controller | Proportion...  
3. What is Direct Action and Reverse Action - Understanding Process Controller Action
   • What is Direct Action and Reverse Act...  
4. What is Closed Loop Control System and Open Loop Control System
   • What is Closed Loop Control System  a...  
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Keep Supporting us.
|| LIKE || COMMENT || SUBSCRIBE
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
#DPT_Re-Range_Calculation
#Revised_Flow_Range
#DP_Flow_Transmitter
#DPT_Range_Calculation
#Differentail_Pressure_Range
#flow_transmitter
#dp_transmitter
#differential_pressure_transmitter
#dpt_range_calculation
#dpt_range_calculator
#differential_pressure_transmitter
#differential_pressure_transmitter_installation
#differential_flowmeter
#differential_flow_transmitter_calibration
#differential_flow_meter_working_principle
#Calculate_Flow_Transmitter_Range

Комментарии

Информация по комментариям в разработке