Hard Shut Off TXVs

Описание к видео Hard Shut Off TXVs

(Audio Only) Jamie Kitchen returns to the podcast and talks all about hard shut off TXVs/TEVs. He discusses bleed and non-bleed valves and why the TXV type matters to your compressor.

When it comes to TXVs, there are two main types: bleed and non-bleed. The former may be referred to as a bleed TXV, and the latter may simply be called a TXV. However, OEMs may refer to TXVs as a "hard shut off TXV" (HSO), which is a non-bleed TXV.

The core difference between bleed and non-bleed TXVs is the equalization speed. That equalization speed affects how your compressor runs; equalizing the system reduces the pressure differential that the compressor will have to overcome on startup. Non-bleed/hard shut off TXVs may cause the compressor to draw locked rotor amps because the pressures did not equalize. To mitigate that issue, you can put in a start cap and relay on the compressor or replace the valve with a bleed TXV.

The main purpose of hard shut off TXVs is to prevent refrigerant migration and flooded starts when the system is off. The non-bleed TXV does not permit equalization, which builds pressure and but keeps refrigerant in the condenser, not the evaporator. Although the compressor will have to overcome more pressure upon startup, it will be less likely to fail due to a flooded start. However, some manufacturers may recommend using a hard start kit to overcome that pressure if you use a hard shut off TXV (even on scroll compressors!).

Jamie and Bryan also discuss:

Non-bleed TXVs on scroll compressors
Pressure rising and falling throughout the system
Opening/closing forces
Superheat spring
Liquid refrigerant migration
Shutting off the suction line vs. using a liquid line solenoid valve
Proper equipment sizing and short-cycling
Charging with bleed vs. non-bleed TXVs
Energy benefits

Read all the tech tips, take the quizzes, and find our handy calculators at https://www.hvacrschool.com/

Комментарии

Информация по комментариям в разработке