Here is a quick video of a full system upgrade that we completed over the winter in a large hotel/conference center. We ripped out an old Notifier system 5000 with an AMG and a fire fighters telephone system and replaced it with a Farenhyt IFP-300ECS that is capable of doing even more! You’ll see at the end of the video there were a few System Sensor HRL horns that were chirping. Upon demoing the old system, we rang the building to make sure everything worked before we did anything so we knew in case parts of the new system didn’t work (thankfully the installation was as smooth as butter) I had multiple short circuit troubles and the horns were the cause because they were on the speaker circuits and not regular NAC’s. So this goes to show that you can’t put regular horns on speaker circuits. Enjoy!