Prospective Fault Current PSCC, PEFC, PFC and External Earth Fault Loop Impedance Ze - Live Tests

Описание к видео Prospective Fault Current PSCC, PEFC, PFC and External Earth Fault Loop Impedance Ze - Live Tests

In this video Marcus carries out using the 2 lead high setting on his Megger MFT tester the external earth fault loop impedance (Ze) and prospective fault current tests. These live tests are carried out from inside the consumer unit (fuse board or fuse box) and will confirm the incoming supply has a connection to Earth and that the overcurrent protective devices can withstand the possible high levels of fault current.

== 🕐 Time Stamps - Cut to the action 🕕 ==

00:00 - External earth fault loop impedance and PSC tests
00:16 - 2 lead high test trips the RCD
00:28 - 2 lead high setting on our Megger MFT tester
00:52 - Disconnected earthing conductor
02:01 - The whole installation is off
02:19 - Ze reading
02:24 - Maximum Ze for TN-C-S and TN-S earthing systems
02:45 - Prospective earth fault current test
03:29 - Prospective short circuit current test
04:21 - Record the highest reading Ipf