How to Install a Potter VSR Vane Waterflow Switch

Описание к видео How to Install a Potter VSR Vane Waterflow Switch

Just a quick video on how to install, adjust, and test a Potter VSR waterflow switch. I'm sorry when I was installing the switch on the pipe I said 10ft-lb of torque, I meant to say 20ft-lb. I also said the switch should be installed 24" from an alarm valve, I got lost in thought but what I meant to say was the switch SHOULD be installed 24" from any valve (control valve, check valve, alarm valve, drain valve, etc). At the very end of the video I mentioned testing the flow switch that is already wired- ALWAYS CHECK VOLTAGE WITH A METER BEFORE REMOVING WIRES JUST IN CASE IT'S HOOKED UP TO A 120V ELECTRIC BELL. I'm actually going to remove this video tomorrow and edit this in as I really don't want anyone getting hurt because they didn't read this (my fault for not mentioning that in the video).

00:00- VSR flow switch specs/general installation good practice
02:38- Installing the VSR flow switch. Proper Hole size for drilling and pipe preoperation
10:25- Inside the VSR flow switch- how the switch works, and how to adjust the time delay
12:11- 2 pole switch (what does that mean?)
13:00- Is it acceptable to pull the lever inside the switch to test the switch?- NO
13:30- Installing a proper test connection for mechanically flow testing the VSR flow switch
15:22- Testing the VSR flow switch with a multimeter
16:33- How does the time delay work on the VSR flow switch? Testing the delay with a multimeter
19:12- Where would I install a VSR flow switch?
20:20- VSR flow switches on a Shotgun riser application
25:00- VSR flow switches on Large/High volume wet system applications
30:40- Testing the VSR flowswitch on an existing building that is already wired up to the fire alarm panel.
31:50- Checking existing wires for voltage

Комментарии

Информация по комментариям в разработке