Return Bends in Sprinkler System & hydraulic Calculations Mistakes related to Return Bend l NFPA 13

Описание к видео Return Bends in Sprinkler System & hydraulic Calculations Mistakes related to Return Bend l NFPA 13

WHEN RETURN BEND IS REQUIRED?
Return bends shall be used where pendent sprinklers are supplied from a raw water source, a mill pond, or open-top reservoirs.

WHERE RETURN BEND IS NOT REQUIRED?
Return bends shall not be required for deluge systems.
Return bends shall not be required where dry pendent sprinklers are used.
Return bends shall not be required for wet pipe systems where sprinklers with a nominal K-factor of K-11.2 or larger are used.

WHAT ARE THE ADVANTAGES OF USING RETURN BEND?
Return bends are used basically to avoid accumulation of sediment in the drop nipples so, it shall be connected to the top of branch lines in accordance with figure below.

WHAT ARE THE COMPONENTS OF RETURN BEND?
1-Arm over: A horizontal pipe that extends from the branch line to a single sprinkler or a sprinkler above and below a ceiling.
2-Riser nipple: A vertical pipe between the cross main and branch line.
3-Branch line: The pipes supplying sprinklers, either directly or through sprigs, drops, return bends, or arm-overs.
4-Hanger: A device or assembly used to support the gravity load of the system piping.
5-Pendant sprinkler: A sprinkler designed to be installed in such a way that the water stream is directed downward against the deflector.

For More Firefighting Videos, Please use the below Links:-

Pipe Schedule Method for Sprinkler System Design l Fire Pipe Sizing using NFPA 13 l Important Rules🔥-
   • Pipe Schedule Method for Sprinkler Sy...  

Firefighting system Pump Room Design-Part-1-    • Part-1-Fire Pump Room Design l Firefi...  

Firefighting system Pump Room Design-Part-2-    • Part 2-Fire Pump Room Design l Firefi...  

Firefighting System Selection for Buildings-Part-1-    • Part 1-Firefighting System Selection ...  

Firefighting System Selection for Buildings-Part-2-    • Part-2-Firefighting System Selection ...  

Jockey Pumps Sizing Calculation-    • Firefighting Pumps-Jockey Pump Sizing...  

Fire Pumps Performance Curves-    • Pump Performance Curves l NFPA 20 l U...  

Fire Pumps Pressure Setting-    • Fire Pump Pressure Setting l NFPA 20 ...  

Missing Information in the NFPA-Technical Discussion-    • Missing information in the NFPA l Imp...  

Firefighting system Pipes & Fittings l Types of Approvals & its limitations l Questions & Answers
   • Firefighting system Pipes & Fittings ...  

Firefighting System-Sprinkler Design-How to Measure the Hydraulic Area l NFPA 13=    • Firefighting System-Sprinkler Design-...  

Part-1-Top 30 Important Firefighting Questions and Answers l Technical Questions for Interview=    • Part-1-Top 30 Important Firefighting ...  

Firefighting system- Sprinkler Design-Hydraulic Calculations with Practical Design Issues-NFPA 13- Chapter 1-Part 1 =    • Chapter 1-Part 1-Sprinkler System Des...  

NFPA 13, NFPA 13R, NFPA 13D, NFPA 101, IBC Standards Requirements for Sprinklers in Bathroom=    • NFPA 13, NFPA 13R, NFPA 13D, NFPA 101...  


Email for your Technical Doubts Discussion: [email protected]
To Join in the online course- +919952785376 or +971543402687
Telegram: https://t.me/+SX6DWcKOgyYxNmI8

Комментарии

Информация по комментариям в разработке