GS3 Durapulse saving program to Drive from HMI

Описание к видео GS3 Durapulse saving program to Drive from HMI

Sorry for poor video/ noise quietly this video was not filmed to be shared originally as I was showing one of my E&I techs how to use Durapulse copy keypad function. I am not responsible for any harm that may be done in the case of wrong parameters being changed in process.

In this video I got through the steps of loading a saved program from HMI to Durapulse drive.

In order this function be unlocked you must have all faults cleared which in this case I didn’t have a thermistor hooked up so I had to disable parameter 3.02 to 99 then reset fault.

Steps to saving keypad to either drive or hmi

-go to parameter page 9.00
-click parameter 9.40 and change it to 1
-go back to parameters and scroll into you see copy keypad
-enter chose between writing to drive or writing to keypad.
-in this case we chose to write to drive, choose where you would like to save or upload your program. Durapulse has the ability to save up to 4 different programs on HMI.
enter on program you desire to uploaded and then your all set.