How to Size a Motor using WOLF method

Описание к видео How to Size a Motor using WOLF method

In this video we talk about how to size a motor using the WOLF method. What is the WOLF method? Well it is a simple way to size the conductors as well as sizing the Over loads and the Fuse.

W = FLC x125%


OL = FLA x art 430.32 depending on the nameplate info

F = FLC x art 430.52 depending on type of fuse or breaker


To find the FLC you need to refer to the NEC in Article 430.247 - 430.250.

FLC - Full Load Current
FLA - Full load Amps