How to disable the detected error Input Phase Fault in Altivar Process Drive ATV630, ATV930, ATV650?

Описание к видео How to disable the detected error Input Phase Fault in Altivar Process Drive ATV630, ATV930, ATV650?

𝙃𝙤𝙬 𝙩𝙤 𝙙𝙞𝙨𝙖𝙗𝙡𝙚 𝙩𝙝𝙚 𝙙𝙚𝙩𝙚𝙘𝙩𝙚𝙙 𝙚𝙧𝙧𝙤𝙧 𝙄𝙣𝙥𝙪𝙩 𝙋𝙝𝙖𝙨𝙚 𝙁𝙖𝙪𝙡𝙩 𝙞𝙣 𝘼𝙡𝙩𝙞𝙫𝙖𝙧 𝙋𝙧𝙤𝙘𝙚𝙨𝙨 𝘿𝙧𝙞𝙫𝙚 (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)??

𝕃𝕚𝕜𝕖👍 𝕊𝕙𝕒𝕣𝕖 🔂 & 𝕊𝕦𝕓𝕤𝕔𝕣𝕚𝕓𝕖👆


#ATV630 #ATV930 #ATV650 #ATV950 #ATV660 #ATV960 #ATV680 #ATV980
#schneider
   • How to disable the detected error Inp...  

Cause:
Principle:
• Loss of one phase on the input side of the drive

Probable cause:
• Drive incorrectly supplied or a tripped fused.
• One phase missing.
• 3-phase drive used on a single-phase supply mains.
• Unbalanced load.
Remedies:
• Check the power connection and the fuses.
• Use a 3-phase supply mains.
• Disable the detected error by [Input phase loss] IPL = [No] no if single phase supply mains or DC bus supply is used for programming only