Configuring Danfoss VLT Micro FC51 for Process closed loop system using 2-wire Pressure transmitter

Описание к видео Configuring Danfoss VLT Micro FC51 for Process closed loop system using 2-wire Pressure transmitter

Two wire start stop with process closed loop system using two wire pressure transmitter for Danfoss VLT Micro FC51 Drive || Digicon Automation

Parameters :-

1-00 Configuration Mode [ 3 ] Process
1-01 Motor Control Principle [ 0 ] u/f
1-20 Motor Power As per motor name plate
1-22 Motor Voltage As per motor name plate
1-23 Motor Frequency As per motor name plate
1-24 Motor Current As per motor name plate
1-25 Motor Nominal Speed As per motor name plate
3-03 Max. Reference (Set-Point) 3.5 Bar
3-10 Preset Reference 100
3-15 Reference Resource 1 [ 0 ] No function
3-16 Reference Resource 2 [ 0 ] No function
3-17 Reference Resource 3 [ 0 ] No function
3-41 Ramp 1 Up Time 25 sec
3-42 Ramp 1 Down Time 40 sec
4-10 Motor Speed Direction [ 0 ] Clockwise
4-14 Motor Speed High Limit 50Hz
4-16 Torque Limit Motor Mode 250%
4-17 Torque Limit Generator Mode 250%
5-10 Terminal 18 Digital Input [ 8 ] Start
5-11 Terminal 19 Digital Input [ 0 ] No function
5-12 Terminal 27 Digital Input [ 0 ] No function
5-13 Terminal 29 Digital Input [ 0 ] No function
5-15 Terminal 33 Digital Input [ 0 ] No function
6-22 Terminal 60 Low Current 4.00 mA
6-23 Terminal 60 High Current 20.00 mA
6-24 Terminal 60 Low Ref. / Feedback Value 0.0 Bar
6-25 Terminal 60 High Ref. / Feedback Value 10.0 Bar
7-20 Process CL Feedback 1 Resource [ 2 ] Analog Input 60
7-33 Process Pi Proportional Gain 2
7-34 Process Pi Integral Time 7