Configuring Danfoss VLT Drives for Two Wire Start / Stop with Speed Up / Down || Digicon Automation

Описание к видео Configuring Danfoss VLT Drives for Two Wire Start / Stop with Speed Up / Down || Digicon Automation

|| Two wire start stop with Speed up / down push button application ||

Parameter list for Two wire start stop with speed up and speed down application :

1-20 = Motor Power [kW] [hp]
1-22 = Motor Voltage
1-23 = Motor Frequency
1-24 = Motor current
1-25 = Motor Nominal Speed
3-41 = Acceleration Time
3-42 = Deceleration Time
5-10 = [ 8 ] Start
5-12 = [ 19 ] Freeze - reference
5-13 = [ 21 ] Speed- up
5-15 = [ 22 ] Speed- down

Комментарии