Density Area Curves l NFPA 13 Important Special Rules l Shortcut for Fire Pump Sizing

Описание к видео Density Area Curves l NFPA 13 Important Special Rules l Shortcut for Fire Pump Sizing

The density/area method can be generally defined as a given amount of water (sprinkler discharge rate) over a specified area. This given amount of water is known as the design density, which is intended to provide cooling and wet adjacent surfaces with the goal of controlling an unintended fire until it can be fully extinguished by emergency services.

The area is the expected area of sprinkler operation, or remote area for which the given amount of water (design density) must be applied. For water demand calculations, it’s assumed all sprinklers in this area will operate. This area is often adjusted for things like quick-response sprinklers, sloped ceilings, dry-pipe, double interlock systems, and high-temperature sprinklers.

Remote area:-
When calculating the water demand needed for the system it is imperative that the correct location on the sprinkler system be chosen as the remote area. Although most fire sprinkler system calculations are done utilizing hydraulic calculation software, many are integrated into computer aided drafting (CAD) programs. The ability of the program to correctly calculate the water demand is directly related to the user’s ability to select the correct area.

The area selected should be the hydraulically most demanding, which is often physically the furthest point from the sprinkler riser on the system. However, in some instances, pipe sizes may make an area physically closer to the riser more hydraulically demanding. An example of this may be an instance closer to the sprinkler riser, which utilizes a more condensed spacing than the physically most remote portion of the system. When in doubt, it is best to calculate multiple areas.

For detailed information about Hydraulic Area calculation, please watch the video, link in below description.

For More Firefighting Videos, Please use the below Links:-
Firefighting system Pump Room Design-Part-1-    • Part-1-Fire Pump Room Design l Firefi...  

Firefighting system Pump Room Design-Part-2-    • Part 2-Fire Pump Room Design l Firefi...  

Firefighting System Selection for Buildings-Part-1-    • Part 1-Firefighting System Selection ...  

Firefighting System Selection for Buildings-Part-2-    • Part-2-Firefighting System Selection ...  

Pipe Schedule Method for Sprinkler System Design l Fire Pipe Sizing using NFPA 13 l Important Rules🔥-
   • Pipe Schedule Method for Sprinkler Sy...  

Return Bends in Sprinkler System & hydraulic Calculations Mistakes related to Return Bend l NFPA 13-
   • Return Bends in Sprinkler System & hy...  

Jockey Pumps Sizing Calculation-    • Firefighting Pumps-Jockey Pump Sizing...  

Fire Pumps Performance Curves-    • Pump Performance Curves l NFPA 20 l U...  

Fire Pumps Pressure Setting-    • Fire Pump Pressure Setting l NFPA 20 ...  

Missing Information in the NFPA-Technical Discussion-    • Missing information in the NFPA l Imp...  

Firefighting system Pipes & Fittings l Types of Approvals & its limitations l Questions & Answers
   • Firefighting system Pipes & Fittings ...  

Firefighting System-Sprinkler Design-How to Measure the Hydraulic Area l NFPA 13=    • Firefighting System-Sprinkler Design-...  

Part-1-Top 30 Important Firefighting Questions and Answers l Technical Questions for Interview=    • Part-1-Top 30 Important Firefighting ...  

Firefighting system- Sprinkler Design-Hydraulic Calculations with Practical Design Issues-NFPA 13- Chapter 1-Part 1 =    • Chapter 1-Part 1-Sprinkler System Des...  
NFPA 13, NFPA 13R, NFPA 13D, NFPA 101, IBC Standards Requirements for Sprinklers in Bathroom=    • NFPA 13, NFPA 13R, NFPA 13D, NFPA 101...  


Email for your Technical Doubts Discussion: [email protected]
To Join in the online course- +919952785376 or +971543402687
Telegram: https://t.me/+SX6DWcKOgyYxNmI8

Комментарии

Информация по комментариям в разработке