BS 7671 Testing RCD’s - Regardless of the Type of RCD Test it as if it is an AC RCD at x1 ONLY

Описание к видео BS 7671 Testing RCD’s - Regardless of the Type of RCD Test it as if it is an AC RCD at x1 ONLY

Changes to BS 7671 under Amendment 2 of the 18th Edition of the Wiring Regulation requires RCD’s to only be tested on the AC setting regardless of the Type of RCD and at the rated residual operating current of the device. This simplifies the testing process so even if you have an A, B or F Type RCD you only need to test it on the AC setting of you MFT tester and at 1x its mA current rating with a maximum disconnection time of 300 ms.

== 🕐 Time Stamps - Cut to the action 🕕 ==

00:00 - How to test an RCD regardless of its TYPE
00:14 - New Amendment 2 of BS7671 18th Edition Wiring Regulation
00:36 - Regardless of type test it as an AC RCD
00:44 - BS7671
00:58 - 1 x value test only
01:09 - MFT tester set up
01:34 - Both half's of the waveform
01:45 - Record the highest of the 2 reading
02:04 - Maximum disconnection time of 300 ms
02:54 - Test the RCD as an AC one regardless of type
02:58 - Different types of RCD

Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.